0 232 464 07 01

Call For Your Questions

0 532 620 60 47

Send a WhatsApp Message

Tinned Copper Conductor

Nitrile Insulation

Nitrile Sheath

Elevator and Submersible Pump Cables

Sartel Nitrile Flat Cable

60227 IEC 71-f 450/750 V

TS IEC 60227-6

Construction

1- Tinned Copper Conductor
2- Nitrile Insulation
3- Nitrile Sheath

Construction

Nitrile insulated and nitrile outer sheath cable with fine stranded copper conductor.

Technical Data

These cables are produced in accordance with the TS IEC 60227-6 standard.

  • Operating Temp.: 70º C
  • Short Circuit Temp.: 160º C
Applications

It is used in places where mechanical stresses are low and as a submersible pump cable in water.

Maksimum İşletme Sıcaklığı

Max. Operating Temp.

Kısa Devre Sıcaklığı

Short Circuit Temp.

Aleve Dayanıklı IEC 60332-1

IEC 60332-1

Esnek Kablo

Rigit

Kurşunsuz

Short Circuit Temp.

Yağa Dayanıklı

Oil Resistant

Test Gerilimi (AC)

Test Voltage (AC)

Serim Sıcaklığı

Installation Temp.

Seri Üretim Bandı

Fast Production Line

Tatlı / Tuzlu Suda

Normal and Salty Water

Hareketli İş Makinaları

Moving Building Mach.

Dalgıç Motor

Submersible Pump

Technical Data

CROSS SECTIONUSED IN COPPER DIAMETERINSULATION THICKNESSOUTER SHEATH WIDTHOUTER SHEATH THICKNESSTOTAL WEIGHTCURRENT CARRYING CAPACITY
mm²mmmmmmmmgr/mtA
FLAT CABLES FOR FLEXIBLE CONNECTIONS
3X1,527/0,2500,7012,405,1010224
3X2,545/0,2500,8014,007,0017532
3X450/0,3000,8016,007,2022942
3X674/0,3000,8019,208,5033054
3X1073/0,4001,0023,509,5051573
3X16112/0,4001,1026,7011,5070398
3X25175/0,4001,2031,5013,001040129
3X35225/0,4001,20---158
3X50365/0,4001,40---198
3X70511/0,4000,70---245
4X1,527/0,2500,8015,305,4014824
4X2,545/0,2500,8019,008,0024032
4X450/0,3000,8021,008,0030942
4X674/0,3001,0023,008,5037154
4X1073/0,4001,1029,0010,0062273
4X16112/0,4001,2035,0012,0093198
4X25175/0,4001,20---129
4X35225/0,4001,20---158
4X50365/0,4001,40---198
3X16+10-1,10-1,00---98
3X25+16-1,20-1,10---129
3X35+16-1,20-1,10---158
3X50+25-1,40-1,20---198