0 232 464 07 01

Call For Your Questions

0 532 620 60 47

Send a WhatsApp Message

Copper Conductor

PVC Insulation

Filler

Galvanized Round Steel Wire Armor

Polyester Tape

PVC Sheath

Low Voltage Cables

Sartel Steel Armored NYY YVOV NYRGY YRY

YVOV 0,6/1 kV

TS IEC 60502-1

NYRGY 0,6/1 kV

VDE 0271

YRY 0,6/1 kV

EC 60502-1
Construction

1- Copper Conductor
2- PVC Insulation
3- Filler
4- Galvanized Round Steel Wire Armor
5- Polyester Tape
6- PVC Sheath

Construction

Single or multicore PVC insulated, PVC sheathed cables with solid or stranded copper conductors with armor of galvanized round steel wires.

Technical Data

These cables are produced in accordance with TS IEC 60502-1, IEC 60502-1 and VDE 0271.

  • Operating Temp.: 70ºC
  • Short Circuit Temp.:: 160ºC

( for short circuit duration up to t<5 sec. )

Applications

These cables are resistant against outer mechanical reactions with their armors of galvanized steel wires. They are suitable for heavy operating conditions, laying and installation. Used under ground and under normal and salty water if specially produced.

Maksimum İşletme Sıcaklığı

Max. Operating Temp.

Kısa Devre Sıcaklığı

Short Circuit Temp.

Aleve Dayanıklı IEC 60332-1

IEC 60332-1

Esnek Kablo

Rigit

Darbelere Dayanıklı

Impact Resistance

Kurşunsuz

Lead Free

Test Gerilimi (AC)

Test Voltage (AC)

Serim Sıcaklığı

Installation Temp.

Toprak Altında

Direct Buried

Tatlı / Tuzlu Suda

Normal and Salty Water

Technical Data

RELATED CROSS-SECTIONCU FACTOROVERALL DIAMETER OF CABLE (Approx.)NET WEIGHT (Approx.)CONDUCTOR DCC RESISTANCE AT 20°CCURRENT CARRYING CAPACITY IN DELIVERY LENGTH (Approx.)
ConduitAir
mm²1000mmmkg/kmΩ / kmAAm
3 CORES
3 X 1,54313,837112,12719,51000
3 X 2,57214,64277,4136261000
3 X 411517,36534,6147341000
3 X 617318,37463,0859441000
3 X 1028820,09451,8379601000
3 X 1646121,010701,15102801000
4 CORES
4 X 1,55814,641212,12719,51000
4 X 2,59615,54847,4136261000
4 X 415418,37244,6147341000
4 X 623019,58583,0859441000
4 X 1038421,410971,8379601000